Technical Specifications
* Function: AC/DC leakage current, low current test
* CT size: 16mm x 18mm
* Range: AC/DC 0mA~60.0A
* Voltage output: Two-speed output: 0mA~6A, 100mV/A; 6A~60A, 10mV/A;
* Resolution: AC/DC: 1mA
* Accuracy: ±3.0%FS (50Hz/60Hz; 23°C±2°C)
* Linearity: ≤2.0%
* Phase error: ≤3°(50Hz/60Hz; 23°C±2°C)
* Power Consumption: ≤5mA
* Output method: Voltage sensing output
* Output connector: BNC plug
* Output line: 2-core shielded cable, length: 1.5 meters for BNC connector
* Detection method: Clamp CT, non-contact measurement
* Zero adjustment: Adjust ZERO key can be zero, eliminate the interference of geomagnetic field and external electric field
* Frequency response: AC: 45Hz ~ 400Hz; DC: 10Hz ~ 10kHz
* Wire position: The tested wire is in the center of the jaws
* Line voltage: below AC 600V circuit test
* Working environment: -10°C~50°C; 80%R below (-10°C~0°C and 40°C~50°C, the maximum increase of error is ±2%FS)
* Storage environment: -10°C~60°C; 70%Rh or less
* Insulation strength: AC3700V/rms (between core and shell)
* Suitable for safety regulations: IEC1010-1, IEC1010-2-032, Pollution Degree 2, CAT III (600V)
* Weight: 200g
* Size: Lx W x H: 215mm×65mm×34mm
* Power supply: 9V DC 6LR61 alkaline dry battery, (Battery not included in the package)continuous use for 100 hours, you can draw out the power cord as needed, external power supply, easy to work for a long time